Viewed 2887 Times 0 Comments

To avoid wrong wiring – the LT & PQ have automatic mode to swap the current line when it feels negative power.

In this auto mode – you can’t read import/export.

You should set the mode to ‘FIX’.

To set this goto Technical menu -> Wirring -> Current Lines and set it to FIX.

 

To do so in PQ goto Technical menu and when asked for password

Enter code 201 – for auto mode

Enter code 202 – for fix mode

Now – when the system is in FIX mode – double check the L&K current wiring – as the Elnet don’t swap it to correct wrong wiring..

In FIX mode the Elnet works correctly with Import / Export energy.

 

To check correct wiring you can also enter code 11 when asked for password.

 

Was this answer helpful ? Yes (0) / No (0)